Traduciendo...
F13.17

Permanent high level in data line

SEW Eurodrive · MOVIDRIVE system

¿Qué significa F13.17 ?

The data signal from Encoder 1 is persistently at a high level. This typically points to a wiring problem (e.g., short to supply voltage) or a defect within the encoder unit, resulting in lost or incorrect position feedback and impacting precise drive control.

Causas comunes

  • Partial or intermittent short circuit between the encoder data line and the +24VDC supply voltage.
  • Degraded internal pull-down resistor within the encoder's data output stage, failing to pull the line low.
  • Accumulated moisture or contaminants in the encoder connector causing a resistive path to the supply.
  • Faulty input stage on the drive's encoder interface, unable to correctly read the data line's low state.
  • Cable insulation breakdown allowing intermittent contact with a supply voltage line.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    With the encoder disconnected, measure the voltage on the affected data line terminal (e.g., X10/Data+) on the drive's side; it should not be consistently high.

  2. 2

    Visually inspect the encoder connector and cable for signs of moisture, corrosion, or physical damage, especially near splice points.

  3. 3

    Perform a resistance test on the encoder cable between the data line and the +24VDC wire, looking for low resistance values (e.g., below 10 kOhms).

  4. 4

    Clean the encoder connector pins using approved electrical contact cleaner and ensure they are dry before reconnection.

  5. 5

    Temporarily replace the encoder cable with a shorter, shielded test cable to rule out cable issues.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: SEW Eurodrive MOVIDRIVE system