01
Overcurrent
SEW Eurodrive · MOVIDRIVE compact System (MCF/MCV/MCS4_A)
¿Qué significa 01 ?
Immediate shut-off due to a short circuit at the inverter output, an oversized motor connected, or a faulty output stage within the inverter. This condition can lead to component stress and potential damage to the drive.
Causas comunes
- Motor current exceeds the safe operating limit (e.g., above P1-OC).
- Mechanical overload on the driven equipment.
- Faulty motor or drive electronics causing excessive current draw.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Rectify any detected short circuit at the inverter output terminals.
- 2
Verify the connected motor's nominal current (FLA) is appropriate for the inverter's rating; connect a smaller motor if mismatched.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas