F-35

Ex-e protection operating mode

SEW Eurodrive · MCBSM

¿Qué significa F-35 ?

An incorrect operating mode or parameter set has been selected for an Ex-e motor application, or the frequency points or current limits are improperly configured. This fault is crucial for maintaining safety with explosion-protected motors, preventing operation under non-compliant or potentially hazardous conditions.

Causas comunes

  • Drive operating mode (e.g., P2-30, Motor Control Mode) not set to a specific 'Ex-e motor' or 'Explosion Proof Motor' mode required for certified operation.
  • Frequency limits (e.g., P1-09, Maximum frequency; P1-10, Minimum frequency) configured outside the permissible range for the Ex-e motor's safe operating envelope.
  • Motor current limits (e.g., P1-04, Motor rated current; P2-20, Overload current limit) set higher than the certified current for the connected Ex-e motor, risking overheating.
  • Motor thermal protection parameters (e.g., P2-18, Thermal overload model; P2-19, I²t time constant) incorrectly configured or disabled, compromising Ex-e certification.
  • Drive not recognized as compatible or certified for operation with the specific Ex-e motor, or parameters not adhering to the motor's ATEX/IECEx certificate.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Refer to the Ex-e motor's specific ATEX/IECEx certification documentation and the drive's manual for certified parameter settings for Ex-e applications.

  2. 2

    Verify Parameter P2-30 (Motor Control Mode) is set to the correct operating mode specifically designated for Ex-e motors, if available, or a certified 'Vector Control' mode with appropriate limits.

  3. 3

    Confirm that Parameter P1-09 (Maximum frequency) and P1-10 (Minimum frequency) are within the frequency range specified in the Ex-e motor's certification.

  4. 4

    Check Parameter P1-04 (Motor rated current) and P2-20 (Overload current limit) to ensure they do not exceed the motor's certified maximum current rating (e.g., I_N).

  5. 5

    Ensure motor thermal protection (P2-18, Thermal overload model; P2-19, I²t time constant) is enabled and correctly configured according to the Ex-e motor's specifications.

  6. 6

    Verify that the drive itself is certified for use with Ex-e motors and that all required protective features (e.g., motor temperature monitoring, current limitation) are active and correctly parameterized.

Ver todos los códigos en este manual (50)
Datos técnicos verificados. Última actualización: March 2026