82
Output Phases Interrupted
SEW Eurodrive · MOVIMOT® MM..D with AC Motor DT/DV / Operating Instruc
¿Qué significa 82 ?
This fault indicates that two or all output phases between the MOVIMOT inverter and the motor are interrupted or open. This prevents current delivery to the motor windings, leading to motor non-operation and potential inverter damage if operated under such conditions.
Causas comunes
- Two or all output phases are interrupted.
- Rated motor power is too small in relation to the rated inverter power.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the connection between the MOVIMOT inverter and the motor for interrupted output phases.
- 2
Verify that the rated motor power is appropriately matched with the rated inverter power.
- 3
Reset the fault by switching off and then switching on the DC 24V supply voltage.
- 4
Reset the error via the error reset function.
Datos técnicos verificados. Última actualización: March 2026