F90

BMS Status Lost

Schneider Electric · XW Pro NA Operation Guide

¿Qué significa F90 ?

This Automatic Fault indicates that the XW Pro is not receiving Battery Management System (BMS) status data from the gateway device. This communication loss can prevent proper battery management and system operation.

Causas comunes

  • Communication cable (e.g., CAN bus, Ethernet) between the gateway device and the BMS is disconnected, damaged, or improperly terminated.
  • Failure of the gateway device to properly relay BMS data to the XW Pro inverter (e.g., internal software issue).
  • Battery Management System (BMS) itself has powered down, malfunctioned, or stopped broadcasting status messages.
  • Incorrect communication parameters (e.g., baud rate, protocol settings) configured on the gateway or XW Pro (e.g., Parameter C3-01 for CAN baud rate).
  • Network congestion or electromagnetic interference causing data packets to be lost or corrupted between the BMS and XW Pro.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Verify that the Battery Management System (BMS) and gateway device are powered on and their status indicators (e.g., LED for heartbeat, comms) are normal.

  2. 2

    2. Inspect the communication cable (e.g., CAN bus cable, Ethernet cable) between the BMS and gateway device for physical damage and secure connections at both ends.

  3. 3

    3. Check the communication parameters (e.g., baud rate 250kbps) configured in both the gateway and the XW Pro (e.g., using Parameter C3-01).

  4. 4

    4. Access the gateway device's interface to verify that it is actively receiving data from the BMS and forwarding it.

  5. 5

    5. Temporarily disconnect and reconnect the communication cables at both the BMS and gateway to reset the physical layer connection.