-SLF

Serial Link Failure

Schneider Electric · Altivar Machine ATV340 Programming

¿Qué significa -SLF ?

This fault occurs when communication is lost between the drive controller and its connected serial devices, such as a remote keypad display or a MODBUS master controller. This prevents external control, monitoring, or parameter adjustment of the drive, interrupting automated processes. The cause could be physical disconnection, incorrect settings, or device malfunction.

Causas comunes

  • Broken, loose, or improperly terminated communication cable (e.g., RS-485 A/B wires, Ethernet cable) between the drive and master device.
  • Incorrect communication parameters (e.g., baud rate P6-01, parity P6-02, drive address P6-03) configured in the drive or the master controller.
  • Excessive electrical noise or electromagnetic interference (EMI) disrupting the communication signal integrity.
  • Faulty communication module or port on either the drive or the master device (e.g., PLC, HMI).
  • Device address conflict on the communication bus, where multiple devices respond to the same address.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify physical communication cable integrity (e.g., check for cuts, bends) and ensure all connectors are securely seated.

  2. 2

    Confirm all communication parameters (e.g., P6-01 baud rate, P6-02 parity, P6-03 drive address) match the master device settings precisely.

  3. 3

    Check for proper termination resistors (e.g., 120 Ohm for RS-485) at both physical ends of the communication bus.

  4. 4

    Measure communication signal levels (e.g., using an oscilloscope for RS-485) to detect noise or signal degradation.

  5. 5

    Temporarily disconnect other devices from the communication bus to isolate potential address conflicts or faulty devices.

Ver todos los códigos en este manual (13)