Traduciendo...
SnbF

Too Many Starts

Schneider Electric · Altistart 22 Soft Starter

¿Qué significa SnbF ?

The soft starter has exceeded the maximum number of motor starts allowed within a defined time period ('SLG' period, as configured by the 'Snb' parameter). This protection mechanism prevents excessive thermal stress on the motor and soft starter from frequent starting attempts.

Causas comunes

  • Motor application's operational demands require more frequent starts than allowed by the configured 'Snb' (maximum starts per hour) parameter.
  • The 'SLG' (start inhibit grace period) parameter is set too short for the actual start frequency, triggering the fault prematurely.
  • Control system error or faulty external sensor causing inadvertent, rapid cycling of the motor start command.
  • External control system (e.g., PLC) rapidly sending RUN command signals to the soft starter's LI input terminals.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Review the application's process requirements to determine if frequent motor starts are genuinely necessary for operation.

  2. 2

    2. Adjust the 'Snb' (max starts per hour) and 'SLG' (start inhibit grace period) parameters to match application demands, considering motor and starter thermal limits.

  3. 3

    3. Inspect the control logic (PLC/DCS program) for errors that could cause rapid cycling of the motor start command.

  4. 4

    4. Monitor the RUN command signal at the soft starter's LIx input terminals for unintended rapid ON/OFF transitions using a voltmeter.

  5. 5

    5. Verify the motor's load characteristics to ensure it isn't stalling or having difficulty reaching full speed, which can trigger restart attempts.

Ver todos los códigos en este manual (32)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Schneider Electric Altistart 22 Soft Starter