Traduciendo...
EtF

External Detected Fault

Schneider Electric · Altistart 22 Soft Starter

¿Qué significa EtF ?

An external protective device or condition, wired to the soft starter's external fault input, has triggered a trip. This indicates a problem originating from a component or system outside the soft starter itself.

Causas comunes

  • External E-stop circuit (e.g., safety relay, mushroom button) connected to a soft starter digital input (e.g., DI1) has opened.
  • Overload relay (e.g., thermal, electronic) protecting downstream equipment, wired to a soft starter digital input (e.g., DI2), has tripped.
  • Process interlock (e.g., high-level switch, pressure sensor) configured to trip soft starter via digital input (e.g., DI3) has activated.
  • Wiring fault (e.g., loose connection, broken wire) on the external fault input terminal (e.g., terminal 5) preventing proper signal detection.
  • Parameter (e.g., P3-01) configuring the digital input for external fault is incorrectly set (e.g., Normally Closed (NC) instead of Normally Open (NO)).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Identify the specific digital input (e.g., DI1, DI2, DI3) configured for external fault using the relevant parameter (e.g., P3-01, P3-02).

  2. 2

    2. Measure voltage at the identified digital input terminal (e.g., terminal 10 for DI1) relative to common (terminal 0V) to verify its state (e.g., 24VDC active, 0V inactive).

  3. 3

    3. Inspect all external devices (e.g., E-stop button, thermal overload, safety relay contacts) connected in series with the fault input for their tripped status.

  4. 4

    4. Test continuity of wiring from the external fault device's output contacts to the soft starter's digital input terminal (e.g., DI1).

  5. 5

    5. Temporarily bypass the external fault device by shorting the soft starter's digital input terminal (e.g., DI1) to the common terminal (0V) to isolate the fault source.

Ver todos los códigos en este manual (32)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Schneider Electric Altistart 22 Soft Starter