PHF
INPUT PHASE LOSS
Schindler · Altivar 312 Drive
¿Qué significa PHF ?
This fault signifies a loss of one or more input phases to the drive. This can be due to incorrect power connection, a blown fuse, or using a three-phase drive on a single-phase line supply, especially under load. This protection only activates when the drive is operating under load.
Causas comunes
- Incorrect power connection to the drive.
- A blown fuse in one of the input phases.
- Attempting to use a three-phase ATV312 drive on a single-phase line supply.
- Unbalanced load on the drive.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the power connection at the input terminals of the drive and inspect all input fuses.
- 2
Ensure a three-phase line supply is used if the ATV312 is a three-phase model.
- 3
Disable input phase loss detection by setting the [Input phase loss] (IPL) parameter to [No] (nO) in the [FAULT MANAGEMENT] (FLt-) menu (page 94).