Traduciendo...
OP3

Overvoltage During Constant Speed

Schindler · Altivar 212 Variable Frequency Drive

¿Qué significa OP3 ?

This fault indicates an overvoltage condition while the Altivar 212 drive is operating at a constant speed, often due to abnormal input voltage fluctuations, power network issues, or regenerative braking where the load causes the motor to run faster than the drive's output frequency.

Causas comunes

  • Input voltage is fluctuating abnormally.
  • Power network capacity is greater than 200 kVA.
  • Power factor capacitor switching in the supply network.
  • SCR switching on the power network.
  • The drive is regenerating (load causes motor to run at a frequency higher than drive output frequency).
  • Intermittent output phase fault.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Install a line reactor to mitigate input voltage issues.

  2. 2

    Check the input and output circuits for phase loss detection and rectify.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Schindler Altivar 212 Variable Frequency Drive