OL2
Motor Overload
Schindler · Altivar 212 Variable Frequency Drive
¿Qué significa OL2 ?
This fault indicates a motor overload condition, potentially caused by incorrect motor control settings, a jammed motor, continuous low-speed operation, or excessive load from the Altivar 212 drive.
Causas comunes
- Incorrect setting of [Mot cont. mode sel.] (Pt).
- The motor is jammed or mechanically binding.
- Continuous low-speed operation is performed.
- Excessive mechanical load is applied to the motor.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Select the correct setting for parameter [Mot cont. mode sel.] (Pt).
- 2
Check the mechanical load for any binding or obstructions.
- 3
Adjust parameter OLM ([Motor overload prot]) to the overload level that the motor can withstand during low speed operation.