Err5

Com RJ45 Fault

Schindler · Altivar 212 Variable Frequency Drive

¿Qué significa Err5 ?

This fault indicates a serial communication error over the RJ45 connection of the Altivar 212 drive, potentially due to issues with network devices, cabling, or communication settings.

Causas comunes

  • Serial communication error on the RJ45 port.
  • Faulty network control devices or communication cables.
  • Incorrect setting of communication timeout parameter F803 ([Com. time out]).
  • Problem with the remote graphic display option cable.
  • Incorrect setting of network protocol parameter F829 ([Network protocol]).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check all RJ45 network control devices and communication cables for integrity.

  2. 2

    Verify the setting of parameter F803 ([Com. time out]) for proper timeout duration.

  3. 3

    Inspect the remote graphic display option cable for damage or loose connections.

  4. 4

    Check the setting of parameter F829 ([Network protocol]) to ensure it matches the network type.