EPH0
Output Phase Loss Fault
Schindler · Altivar 212 Variable Frequency Drive
¿Qué significa EPH0 ?
This fault is detected when one or more output phases to the motor are lost, leading to an imbalance or interruption in motor current from the Altivar 212 drive. This can severely affect motor operation and cause damage.
Causas comunes
- Loss of one or more output phases.
- Bad connection in the output circuit (U, V, W terminals).
- Output disconnect has opened.
- Open winding in the motor.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Inspect motor cable connections at the drive's output terminals (U/T1, V/T2, W/T3) for tightness and continuity.
- 2
Measure the resistance of motor windings to identify an open circuit.
- 3
Verify the status of any output disconnect devices (e.g., motor contactor).
- 4
Check parameter F605 ([Output phase loss]) setting.
Datos técnicos verificados. Última actualización: March 2026