E-18

VIA Signal Fault

Schindler · Altivar 212 Variable Frequency Drive

¿Qué significa E-18 ?

This fault signifies that the analog input signal at terminal VIA has dropped below the minimum level defined by parameter F633 ([Loss of VIA]), indicating a potential loss of speed reference signal or sensor input.

Causas comunes

  • The analog signal at terminal VIA is below the configured threshold.
  • Incorrect setting of parameter F633 ([Loss of VIA]).
  • Loss of signal from the sensor connected to VIA.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the analog signal voltage/current at terminal VIA.

  2. 2

    Rectify the cause of the signal loss (e.g., sensor, wiring).

  3. 3

    Check parameter F633 ([Loss of VIA]) and verify it is set correctly for the application.