A402.13

Duplicate Refresh Error

Omron · SYSMAC CJ2 CPU Unit

¿Qué significa A402.13 ?

This fault occurs when duplicated refreshing is performed for a Special I/O Unit. When the Duplicate Refresh Error Flag (A402.13) is ON, bit A426.15 indicates the cause of the error, and bits A426.00 to A426.11 contain the unit number (0-95) of the affected Special I/O Unit. The CPU Unit will continue operating, and the ERR/ALM indicator on the front of the CPU Unit will flash.

Causas comunes

  • Configuration error leading to a Special I/O Unit's refresh being duplicated.
  • Incorrect I/O table or PLC Setup settings for a Special I/O Unit.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Identify the affected Special I/O Unit by reading the unit number from A426.00 to A426.11.

  2. 2

    Review the PLC I/O table and configuration settings for the identified Special I/O Unit.

  3. 3

    Ensure that the refreshing mechanism for the Special I/O Unit is configured uniquely.

  4. 4

    Clear the error flags (A402.13, A426.15) and the unit number bits (A426.00 to A426.11) after resolving the configuration issue.

Ver todos los códigos en este manual (27)
Datos técnicos verificados. Última actualización: March 2026