Duplicate Refresh Error
Omron · SYSMAC CJ2 CPU Unit
¿Qué significa A402.13 ?
This fault occurs when duplicated refreshing is performed for a Special I/O Unit. When the Duplicate Refresh Error Flag (A402.13) is ON, bit A426.15 indicates the cause of the error, and bits A426.00 to A426.11 contain the unit number (0-95) of the affected Special I/O Unit. The CPU Unit will continue operating, and the ERR/ALM indicator on the front of the CPU Unit will flash.
Causas comunes
- Configuration error leading to a Special I/O Unit's refresh being duplicated.
- Incorrect I/O table or PLC Setup settings for a Special I/O Unit.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Identify the affected Special I/O Unit by reading the unit number from A426.00 to A426.11.
- 2
Review the PLC I/O table and configuration settings for the identified Special I/O Unit.
- 3
Ensure that the refreshing mechanism for the Special I/O Unit is configured uniquely.
- 4
Clear the error flags (A402.13, A426.15) and the unit number bits (A426.00 to A426.11) after resolving the configuration issue.