A327.09

Pulse Output 3 Interrupt Feeding Error

Omron · SYSMAC CJ2 CPU Unit

¿Qué significa A327.09 ?

This flag turns ON if an overflow or underflow condition occurs when an interrupt input is received for Pulse Output 3. It also indicates an error if overflow/underflow occurs while moving the specified number of pulses after starting output with the IFEED(892) instruction. An ON state of this flag indicates an error condition.

Causas comunes

  • Overflow or underflow condition detected during interrupt input reception for Pulse Output 3.
  • Overflow or underflow occurring while the specified number of pulses is being moved using the IFEED(892) instruction.
  • Incorrect definition of the origin or pulse count parameters when starting IFEED(892) operation for Pulse Output 3.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Review the IFEED(892) instruction parameters for Pulse Output 3 to ensure pulse counts, limits, and origin are correctly configured.

  2. 2

    Monitor the interrupt input signal to ensure its timing, frequency, and integrity are within expected operational limits.

  3. 3

    Verify the processing time of the interrupt task associated with IFEED(892) to prevent missed pulses or timing issues.

  4. 4

    Check for any external noise or signal interference on the interrupt input line for Pulse Output 3.