1-rotation Counter Error
Omron · NJ/NX-series Machine Automation Controller
¿Qué significa 08430000 hex ?
The encoder detected a one-rotation counter error. This implies an issue with the encoder's ability to accurately count single rotations, affecting position feedback.
Causas comunes
- There is excessive noise
- Failure due to vibration, impact, condensation, foreign matter, etc.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the supply voltage at the encoder input terminals to verify it is within the specified nominal range.
- 2
Inspect the entire encoder cable for physical damage, proper shielding, and ensure all connections at the encoder and the Omron NJ/NX controller are secure and correctly terminated.
- 3
Check the mechanical mounting of the encoder to the rotating shaft for any looseness, slippage, or excessive vibration that could affect rotational accuracy.
- 4
Verify the encoder's configuration parameters (e.g., resolution, counting mode, signal type) within the Omron NJ/NX Controller match the specifications of the installed encoder.