External Encoder Data Restoration Error
Omron · NJ/NX-series Machine Automation Controller
¿Qué significa 08180000 hex ?
Initialization of internal position data was not processed correctly in Fully-closed Control Mode and Absolute Value Mode. This is similar to the internal encoder error but specific to external encoders used in fully-closed loop systems.
Causas comunes
- There is insufficient power supply voltage for the external encoder.
- Noise is entering on the external encoder line.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the external encoder's power supply voltage at the encoder terminals and controller input against manufacturer specifications.
- 2
Inspect all external encoder cabling for physical damage, proper routing, secure connections, and correct shielding termination at both the encoder and controller ends.
- 3
Check Omron Sysmac Studio for correct external encoder module configuration, associated axis parameters (e.g., resolution, scaling, data format), and fully-closed loop settings.
- 4
Perform a controlled power cycle of the Omron NJ/NX controller and associated servo system to force a fresh re-initialization of all connected devices.