080B0000
Safety Input Error
Omron · NJ/NX-series Machine Automation Controller
¿Qué significa 080B0000 ?
One or both of the photocouplers for safety inputs 1 and 2 have transitioned to an OFF state, triggering a safety error. This typically indicates an issue with the safety circuit integrity, such as a physical cable problem.
Causas comunes
- Safety input cable for inputs 1 or 2 is disconnected
- Safety input cable for inputs 1 or 2 is broken
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Visually inspect the cables connected to safety inputs 1 and 2 for physical damage or disconnections.
- 2
Measure continuity of the safety input cables for inputs 1 and 2.