A295.12

Task Error

Omron · CJ-series CJ2 CPU Unit

¿Qué significa A295.12 ?

A task error has occurred, meaning there is no executable cyclic task or no task corresponds to an interrupt that was input. This is particularly critical if the 'Stop CPU on Instruction Error' parameter in the PLC Setup is set to 'Stop', leading to a fatal program error (0x80F0).

Causas comunes

  • No executable cyclic task is defined.
  • No task corresponds to a received interrupt, and the 'Stop CPU on Instruction Error' parameter in PLC Setup is set to 'Stop'.
  • Incorrect startup cyclic task attributes are configured.
  • Task numbers specified in TKON(820), TKOF(821), or MSKS(690) instructions do not have corresponding created tasks.
  • The power OFF interrupt task is enabled in PLC Setup but has not been created.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the startup cyclic task attributes.

  2. 2

    Verify the execution status of each task as controlled by TKON(820) and TKOF(821).

  3. 3

    Confirm that all task numbers specified in TKON(820), TKOF(821), and MSKS(690) instructions have corresponding created tasks.

  4. 4

    Use MSKS(690) to mask any I/O or scheduled interrupt tasks that are not being used and do not have programs set for them.

  5. 5

    If the power OFF interrupt task is enabled in PLC Setup, verify that the power OFF interrupt task has been created.

Ver todos los códigos en este manual (34)