Traduciendo...
0x80E1
Too Many I/O Points Error
Omron · CJ-series CJ2 CPU Unit
¿Qué significa 0x80E1 ?
One or more system limits regarding I/O points, interrupt inputs, Pulse I/O Modules, or Expansion Racks have been exceeded, or resources are allocated to more than one Unit. This is a fatal error, indicated by flag A401.11, with Auxiliary Area A407.13 to A407.15 providing specific details about which limit was exceeded.
Causas comunes
- Total number of I/O points set in the I/O tables exceeds the maximum allowed for the CPU Unit (details bits: 000).
- More than 32 interrupt inputs are configured (details bits: 001).
- Three or more Pulse I/O Modules were connected to a CJ2M CPU Unit (details bits: 100).
- The number of Expansion Racks exceeds the maximum allowed (details bits: 101).
- More than 10 I/O Units are connected to a single Rack (details bits: 111).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Correct the I/O configuration (reduce I/O points, interrupt inputs, Pulse I/O Modules, or Expansion Racks/Units per Rack) according to the details provided in Auxiliary Area A407.13 to A407.15.
- 2
After correcting the configuration, cycle the power supply OFF and back ON.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Omron CJ-series CJ2 CPU Unit