Regenerative brake pre-alarm

Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive

¿Qué significa RB ?

This pre-alarm appears if the regenerative brake duty reaches or exceeds 85% of the value set in Pr.70 (Special regenerative brake duty). It's a warning that the regenerative braking capacity is nearing its limit, and a regenerative overvoltage (E.OV[]) fault may occur if it reaches 100%.

Causas comunes

  • Regenerative braking energy exceeding capacity during deceleration.
  • Regenerative brake resistor approaching thermal limit.
  • High DC bus voltage detected during regenerative braking event.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Set the deceleration time longer to reduce the instantaneous regenerative energy and duty.

  2. 2

    Check the brake resistor duty to ensure it is not too high for the application, possibly requiring a larger resistor.

  3. 3

    Verify the settings of Pr.30 (Regenerative function selection) and Pr.70 (Special regenerative brake duty).