Er1

Write disable error

Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive

¿Qué significa Er1 ?

This error occurs if a parameter setting was attempted while Pr.77 (Parameter write selection) disables write operations, if frequency jump ranges (Pr.31 to Pr.36) overlap, or if communication between the PU (Parameter Unit) and the inverter is abnormal. It indicates an issue preventing parameter modification or a communication problem.

Causas comunes

  • Attempt to write to a protected parameter memory location.
  • Parameter write disabled via a system setting (e.g., P1-01=0).
  • Hardware fault preventing modification of non-volatile memory.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the setting of Pr.77 (Parameter write selection) to ensure parameter writing is enabled.

  2. 2

    Review and correct any overlapping settings in Pr.31 to Pr.36 (frequency jump parameters).

  3. 3

    Check the physical connection between the PU and the inverter for proper communication.

Ver todos los códigos en este manual (55)
Datos técnicos verificados. Última actualización: March 2026