EHR

Ethernet communication fault

Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive

¿Qué significa EHR ?

This fault appears when Ethernet communication is interrupted by physical factors, especially when Pr.1431 (Ethernet signal loss detection function selection) is set to a value between '1' and '3'. It signifies a physical layer problem with the Ethernet connection to the inverter.

Causas comunes

  • Disconnected or damaged Ethernet cable (RJ45 connector, internal conductors).
  • Network switch or router failure preventing data transmission.
  • Incorrect IP address, subnet mask, or gateway settings on the inverter (e.g., Pr.1408 to Pr.1413).
  • Excessive network traffic (broadcast storms) or collisions causing communication timeouts.
  • Physical damage to the inverter's Ethernet port or internal communication module.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the physical Ethernet cable connection at both the inverter and the network switch, ensuring the cable is securely latched.

  2. 2

    Check the link status LEDs on the inverter's Ethernet port and the connected network switch port (should be green/solid).

  3. 3

    Ping the inverter's IP address (set in Pr.1409) from a connected network device to verify basic network connectivity.

  4. 4

    Inspect the Ethernet cable for physical damage (kinks, cuts) and test its continuity using an Ethernet cable tester.

  5. 5

    Review Pr.1431 (Ethernet signal loss detection function selection) and associated timeout parameters to ensure they are appropriate for the network environment.

Ver todos los códigos en este manual (55)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Mitsubishi FR-E800 Variable Frequency Drive