E.OC2

Overcurrent During Constant Speed

Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive

¿Qué significa E.OC2 ?

This fault occurs when the inverter's output current reaches or exceeds approximately 230% of the rated current while operating at a constant speed. This activates the protection circuit, causing the inverter output to shut down. Common causes include sudden load changes, output short-circuits, or incorrect control parameters. Repeated overcurrent can lead to motor and inverter damage.

Causas comunes

  • Excessive continuous mechanical load on the motor, exceeding its rated current capacity.
  • Motor winding short circuit (phase-to-phase or phase-to-ground) occurring during operation.
  • Incorrect motor parameters (e.g., P0-03 motor rated current, P0-06 motor rated frequency) causing miscalculation of load.
  • Intermittent short circuit in motor cables due to insulation damage or vibration.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure actual motor load current with a clamp meter during constant speed operation and compare to motor nameplate and P0-03.

  2. 2

    Inspect driven machinery for mechanical binding, bearing failure, or excessive friction using a torque wrench or by manual rotation.

  3. 3

    Perform a motor winding resistance test (phase-to-phase) and insulation resistance test (winding-to-ground) using a multimeter and megohmmeter respectively.

  4. 4

    Verify motor control parameters (e.g., P0-03, P0-06) against the motor nameplate data for accuracy.

  5. 5

    Check for loose connections or signs of arcing at inverter output terminals (U, V, W) and motor terminal box.

Ver todos los códigos en este manual (55)
Datos técnicos verificados. Última actualización: March 2026