U6
Compressor Overcurrent (Overload) Cut-off
Mitsubishi Electric · R410A Systems
¿Qué significa U6 ?
The compressor has experienced an overcurrent condition due to an overload, leading to a safety cut-off. This could be caused by mechanical issues, excessively high head pressure, or an electrical fault within the compressor motor or associated circuit.
Causas comunes
- Compressor overcurrent due to overload.
- Excessive mechanical load on the compressor.
- Thermal overload protection of the compressor tripped.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure compressor running current on all three phases using a clamp meter — compare measured values to the motor nameplate FLA.
- 2
Measure discharge and suction pressures to rule out high head pressure or liquid slugging as a cause.
- 3
Measure winding resistance of the compressor motor phases (U-V, V-W, U-W) and to ground using an ohmmeter — expect balanced resistance and no ground fault.