Traduciendo...
F2

L3 Open Phase Detection

Mitsubishi Electric · R410A Systems

¿Qué significa F2 ?

The outdoor unit has detected an open circuit in the L3 phase of the main power supply. This indicates a loss of one of the three input phases, potentially leading to unbalanced operation or motor damage.

Causas comunes

  • Loss of power on phase L3.
  • Open circuit in L3 wiring.
  • Faulty connection or fuse on L3.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure voltage between L1-L2, L2-L3, and L3-L1 at the outdoor unit main power terminals — expect balanced 3-phase voltage.

  2. 2

    Inspect all wiring connections for the L3 phase at the outdoor unit's main power terminals for looseness or corrosion.

  3. 3

    Check the integrity of the circuit breaker or fuse protecting the L3 phase in the electrical panel.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Mitsubishi Electric R410A Systems