E36
Abnormally High Discharge Temperature / Refrigerant or THOD Sensor Fault
Mitsubishi Electric · R410A Systems
¿Qué significa E36 ?
The compressor discharge temperature is abnormally high, possibly due to insufficient refrigerant charge or a defective compressor discharge temperature sensor (THOD). High discharge temperatures can lead to compressor damage.
Causas comunes
- Compressor discharge temperature sensor (THOD) fault.
- Abnormally high temperature detected at the compressor discharge.
- Low refrigerant charge or liquid slugging.
- Sensor wiring integrity issue.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the resistance of the THOD sensor at its leads — compare to a resistance-temperature chart if available.
- 2
Measure discharge pressure and temperature at the compressor outlet using manifold gauges and a temperature probe.
- 3
Perform a leak detection test and verify refrigerant charge level — recover, evacuate, and recharge if low.
- 4
Inspect the THOD sensor's connector on the outdoor unit PCB for secure seating and damage.
Datos técnicos verificados. Última actualización: March 2026