EF (6607 or 6608)
Non-Defined Error Code
Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
¿Qué significa EF (6607 or 6608) ?
This code is displayed when the unit receives an undefined error code. Possible root causes include noise in the remote controller transmission wire or indoor/outdoor connecting wire, the outdoor unit not being an inverter model, or the use of an incompatible remote controller model (PAR-S21A).
Causas comunes
- Unspecified error code detected by the system.
- Potential software anomaly or unknown operational state.
- Requires further diagnosis based on system logs.
- Check for other active error codes.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Turn the power off, then on again. If the abnormality reappears, replace the indoor controller board or outdoor controller circuit board.
- 2
If the outdoor unit is not an inverter model, replace it with an inverter model.
- 3
If the remote controller model is PAR-S21A, replace it with an MA remote controller.