E9 (6811)
Indoor/Outdoor Unit Communication Error (Outdoor Transmitting)
Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
¿Qué significa E9 (6811) ?
The outdoor controller circuit board detects '0' receiving 10 times continuously despite transmitting '1', or it fails to find a blank transmission path for 10 minutes. This indicates potential contact failure or looseness in the indoor/outdoor unit connecting wire, a defective communication circuit on the outdoor controller circuit board, or noise interference in the power supply or connecting wire.
Causas comunes
- Outdoor unit fails to transmit communication signals to indoor unit.
- Damaged or disconnected communication wiring between units.
- Faulty outdoor unit control board.
- Interference on the communication line.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check for disconnection or looseness of the indoor/outdoor unit connecting wire.
- 2
Turn the power off, then on again. If the abnormality reappears, replace the outdoor controller circuit board.