Traduciendo...
F10E

Number of Receive Error Retries Exceeded

Mitsubishi Electric · MELSEC Q-series MELSECNET/H

¿Qué significa F10E ?

The system has attempted to receive data multiple times but consistently failed, exceeding the allowed number of retries. This suggests a persistent communication issue on the receiving end.

Causas comunes

  • Persistent network communication problems preventing successful data reception
  • Faulty cables or incorrect wiring
  • Absence of terminating resistors (in bus networks)
  • Duplicate station numbers or duplicate control/master stations
  • Faulty network hardware at the receiving station

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect network cables for physical faults or incorrect wiring

  2. 2

    Verify the presence and correct installation of terminating resistors on the bus network

  3. 3

    Check for sources of electrical noise near network cabling

  4. 4

    Verify station numbers and control/remote master station settings for any duplication

  5. 5

    Check for faulty network hardware at the receiving station

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Mitsubishi Electric MELSEC Q-series MELSECNET/H