Traduciendo...
INPUT-LKG-C1

Input Leakage Current (Contactless Switch)

Mitsubishi Electric · MELSEC iQ-R I/O Module

¿Qué significa INPUT-LKG-C1 ?

A leakage current from a contactless input switch prevents the input signal from reliably turning off. This occurs when the residual voltage across the input module terminals, caused by the leakage current, remains above the module's OFF voltage threshold, leading to an incorrect ON state.

Causas comunes

  • Leakage current from a contactless input switch or other input device is too high.
  • The input module interprets the residual voltage from the leakage current as an ON signal.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Connect an appropriate resistor in parallel across the input terminals to effectively reduce the voltage below the OFF threshold. For AC inputs, consider a CR constant of 0.1 to 0.47µF + 47 to 120Ω (1/2W).

Ver todos los códigos en este manual (56)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Mitsubishi Electric MELSEC iQ-R I/O Module