AC Input Signal Not Turning ON
Mitsubishi Electric · MELSEC iQ-R I/O Module
¿Qué significa AC-INPUT-NO-ON ?
An AC input signal fails to turn on, typically caused by step-like deformations in the input signal waveform around the zero-cross voltage. This issue often arises from power supply quality problems, such as those associated with off-line type Uninterruptible Power Supplies (UPSs).
Causas comunes
- Deformed input signal waveform around the zero-cross voltage, preventing proper detection by the AC input module.
- Use of an off-line type UPS or other power supply that generates insufficient or distorted AC waveforms.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Improve the input signal waveform by using an on-line type UPS or other power conditioning device that provides a cleaner, stable AC waveform.