3060H
Module configuration error
Mitsubishi Electric · MELSEC iQ-R I/O Module
¿Qué significa 3060H ?
An error was detected in the configuration of the module. This may be due to incorrect physical mounting of the module or attempting to use an I/O module that does not support SIL2 mode within a safety-critical paired configuration.
Causas comunes
- Incorrect physical mounting position of the module within the rack or system.
- An I/O module with diagnostic functions that does not support SIL2 mode was incorrectly mounted as part of a SIL2-compliant pair.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the mounting position of each module in the system against the configuration diagram to ensure correctness.
- 2
If operating in SIL2 mode, confirm that the I/O module with diagnostic functions supports SIL2 mode and is correctly installed as a compatible pair.
Datos técnicos verificados. Última actualización: March 2026