Traduciendo...
OC During Acc

Overcurrent shut-off during acceleration

Mitsubishi Electric · FR-E500 Inverter

¿Qué significa OC During Acc ?

The inverter output is shut off because the output current reached or exceeded approximately 200% of the rated current during the acceleration phase. This indicates that the motor load is too high for the acceleration rate, or there is an issue with the motor or wiring.

Causas comunes

  • Motor accelerating too rapidly for the connected load inertia or motor capability.
  • Output short-circuit or ground fault occurring during acceleration.
  • Motor or driven equipment experiencing mechanical binding or excessive friction.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Increase the acceleration time setting (e.g., Pr. 7 or Pr. 44) to allow for a gentler ramp-up.

  2. 2

    Measure the motor load current during acceleration and compare it to the motor nameplate rated current.

  3. 3

    Inspect motor cable and motor terminals for signs of short-circuit or ground fault.

Ver todos los códigos en este manual (17)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Mitsubishi Electric FR-E500 Inverter