Traduciendo...
E32

Mains Power Phase Reversal / Open Phase Detection

Mitsubishi Electric · FR-D700 Inverter

¿Qué significa E32 ?

The anti-phase device has detected that two phases of the mains power need to be swapped, indicating a phase reversal. Alternatively, the L2 phase of the mains power (primary side of contactor) has been detected as open, leading to unbalanced power.

Causas comunes

  • Power supply phase sequence is reversed (e.g., L1-L2-L3 instead of L1-L3-L2).
  • One phase of the main AC power supply is missing (open phase).
  • Internal power module protection against phase reversal.
  • Incorrect wiring at the main power input terminals.
  • Power source unstable with fluctuating phase presence.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the phase sequence of the mains power supply using a phase rotation meter. If reversed, correct the L1, L2, L3 phase connections at the outdoor unit.

  2. 2

    Measure the voltage across all phases (L1-L2, L2-L3, L3-L1) at the primary side of the contactor to check for an open L2 phase.

  3. 3

    Inspect the contactor for proper operation, looking for signs of pitting or loose connections at the terminals.

Ver todos los códigos en este manual (78)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Mitsubishi Electric FR-D700 Inverter