PI

Fault during parameter initialisation

Lenze · 9300 Series

¿Qué significa PI ?

An error was detected during the parameter set transfer between two devices, or the parameter set does not match the controller (e.g., if data was transferred from a higher-power controller to a lower-power controller). This can lead to incorrect drive configuration.

Causas comunes

  • Attempting to transfer a parameter set from a different hardware variant or power rating (e.g., from a 22kW drive to an 11kW drive).
  • Mismatched firmware versions between the source and target devices during parameter transfer, causing structural incompatibilities.
  • Data corruption during serial communication (e.g., RS485, Ethernet) between devices due to noise or incorrect cabling.
  • Insufficient memory space on the target device to accommodate the transferred parameter set (less common).
  • Device power interruption during the critical parameter initialization phase after a transfer or boot-up.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the hardware type and firmware version of both the source and target devices are identical or fully compatible before transferring.

  2. 2

    Use the manufacturer's official software tool to create a compatible parameter file for the specific target device model and firmware.

  3. 3

    Inspect the communication cable (e.g., USB, Ethernet, RS485) between devices for damage or loose connections, replacing if necessary.

  4. 4

    Try to load a factory default parameter set (e.g., using P0-01 = 0) on the target device before attempting a transfer again.

  5. 5

    Ensure a stable power supply to both devices throughout the parameter transfer and initialization process.

  6. 6

    Manually review critical parameters (e.g., motor nominal current P3-00, motor power P3-01) for consistency with the target drive's ratings.