0079

PI (Fault during parameter initialisation)

Lenze · 9300 Series

¿Qué significa 0079 ?

An error was detected during parameter set transfer between two devices, or the parameter set does not match the controller (e.g., higher-power controller data transferred to lower-power). This prevents proper device initialization.

Causas comunes

  • Incompatible hardware version or power rating mismatch between the source and target controllers during parameter transfer.
  • Transfer of a parameter set from a different product series or family to the current device.
  • Software version mismatch between the originating parameter set and the target controller's firmware (C0004).
  • Corruption of the parameter data file during transfer from an external tool (e.g., PC software).
  • Internal memory write protection enabled or memory failure preventing new parameters from being initialized.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the model number and power rating of the controller against the source of the parameter set to confirm compatibility.

  2. 2

    Check the firmware version (C0004) of the target controller and ensure the parameter set is generated for or compatible with this specific version.

  3. 3

    Attempt to initialize the drive with factory default settings by setting C0003 = 1 and then performing a power cycle.

  4. 4

    Use the manufacturer's dedicated software (e.g., Lenze Engineer) to create a new parameter set specifically for the target controller and its firmware.

  5. 5

    Inspect the communication interface (e.g., Ethernet, USB cable) used for parameter transfer for damage or loose connections.

Ver todos los códigos en este manual (145)
Datos técnicos verificados. Última actualización: March 2026