PR4 (Checksum error in parameter set 4)
Lenze · 9300 Series
¿Qué significa 0078 ?
A checksum error has been detected in parameter set 4, indicating a fault during loading or an interruption during transfer via the keypad. This can also occur if saved parameters are incompatible with the loaded software version.
Causas comunes
- Interruption of parameter transfer (e.g., during upload from keypad or communication bus) to parameter set 4.
- Data corruption in the non-volatile memory bank corresponding to parameter set 4.
- Attempting to load a parameter set 4 that was created on an older or incompatible firmware version.
- Power loss or voltage fluctuation during the save operation for parameter set 4.
- Faulty keypad or communication interface transmitting incorrect data for parameter set 4.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Cycle power to the drive and attempt to reload parameter set 4 from a known good backup file using the appropriate software tool.
- 2
Verify the integrity of the parameter set 4 file used for transfer and ensure it matches the current firmware version (C0004).
- 3
If transferring via keypad, ensure a stable connection and retry the transfer of parameter set 4, monitoring for interruptions.
- 4
Set C0003 to 1 (factory default) to clear any corrupted settings, then carefully reconfigure only the necessary parameters in set 4.
- 5
Check the drive's communication bus (e.g., CAN, EtherCAT) for noise or intermittent connections if parameter set 4 transfer occurs over the bus.