OH

Heatsink Overtemperature

Lenze · 8200 Series

¿Qué significa OH ?

The controller's heatsink temperature has exceeded its safe operating limit (either >85°C or >80°C), typically due to high ambient temperature, blocked airflow, or excessive drive load. A dirty heatsink or high currents during acceleration can also contribute. Sustained overtemperature will lead to derating, thermal shutdown, and reduced component lifespan.

Causas comunes

  • High ambient temperature surrounding the drive exceeding its specified operating limit (e.g., >40°C).
  • Blocked or restricted airflow to the heatsink fins due to dust, debris, or improper enclosure design.
  • Cooling fan failure (e.g., FAn1 fault not yet triggered) reducing heat dissipation.
  • Excessive drive load leading to sustained high current output, generating more heat.
  • Dirty heatsink fins restricting heat transfer from the power modules.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Measure the ambient temperature immediately surrounding the drive and ensure it is within the drive's specified operating range.

  2. 2

    2. Disconnect mains power and clean the heatsink fins thoroughly with compressed air to remove dust and debris.

  3. 3

    3. Verify the operation of all cooling fans within the drive by observing rotation and airflow once power is restored.

  4. 4

    4. Ensure proper ventilation within the electrical enclosure, checking for blocked vents or insufficient spacing around the drive.

  5. 5

    5. Monitor the drive's output current (e.g., C0004) to confirm it is within the drive's nominal rating for continuous operation.

Ver todos los códigos en este manual (40)
Datos técnicos verificados. Última actualización: March 2026