Traduciendo...
STA1 (CIB_SR) Off
CIB_SR Microcontroller I/O Node Power Not Present
Kuka · Sunrise Cabinet Med Controller
¿Qué significa STA1 (CIB_SR) Off ?
The STA1 (CIB_SR) Orange LED is OFF, indicating no supply voltage is present for the CIB_SR microcontroller I/O node. This prevents the I/O node from operating and can lead to communication failures or unresponsive I/O.
Causas comunes
- The CIB_SR Microcontroller I/O Node (STA1) is not receiving power.
- Failure of the main power supply to the I/O node.
- Loose or damaged power connection to STA1.
- Fault in the power distribution unit supplying STA1.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check fuse F17.3 on the CCU_SR for continuity and proper rating.
- 2
If the PWR/3.3V LED (Item 6, Page 98) lights up, indicating the 3.3V power is present, exchange the CCU_SR module as the fault is likely internal to the module's power distribution for the I/O node.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Kuka Sunrise Cabinet Med Controller