26119
Power supply failure, KPP/KSP (axis)
Kuka · KR C4 extended
¿Qué significa 26119 ?
The supply voltage to the KPP or KSP module for a specific axis has fallen below 300 V. This indicates an insufficient power supply, potentially causing erratic operation or complete shutdown.
Causas comunes
- Power lead is damaged or disconnected.
- KPP cabling fault.
- Supply voltage dropped below 300V.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Inspect the power lead for damage and proper connection.
- 2
Check KPP cabling for damage and correct connections.
- 3
Reinitialize the drive bus: Power Off / Power On.
- 4
Check the KPP module.
Datos técnicos verificados. Última actualización: March 2026