26107
Intermediate circuit voltage too high, KPP/KSP (axis)
Kuka · KR C4 extended
¿Qué significa 26107 ?
This fault indicates an overvoltage condition in the intermediate DC link circuit during operation. This typically occurs when regenerative energy from braking is not adequately dissipated or if the incoming mains voltage is too high. Sustained overvoltage can damage the DC bus capacitors and power semiconductors of the drive.
Causas comunes
- Excessive load during braking, generating too much regenerative energy.
- Mains voltage exceeding the permissible input range for the drive.
- Malfunction of the ballast switch or braking resistor circuit.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check trace recording of the intermediate circuit voltage.
- 2
Check mains voltage at the input to the drive.
- 3
Check ballast switch for proper operation.
- 4
Reduce excessive load during braking operations.
- 5
Reinitialize the drive bus: Power Off / Power On.
- 6
Check KSP module for faults.