Overcurrent, KPP/KSP (axis)
Kuka · KR C4 extended
¿Qué significa 26034 ?
A brief overcurrent has occurred that exceeds the maximum current rating of the KPP module. This is typically caused by a short-circuit or a sudden, excessive load.
Causas comunes
- Short-circuit in the motor or motor cable.
- Excessive load on the axis.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check trace recording of axis current to identify the overcurrent event.
- 2
Inspect motor for potential faults.
- 3
Inspect motor cable for damage or short-circuits.
- 4
Reinitialize the drive bus: Power Off / Power On.
- 5
Check the KSP module.
- 6
Check the KPP module.