Traduciendo...
26034
Overcurrent, KPP/KSP (axis)
Kuka · KR C4 Controller
¿Qué significa 26034 ?
This fault signifies a brief overcurrent condition that exceeds the maximum current capacity of the KPP drive. This is typically caused by a short-circuit, leading to immediate drive protection actions.
Causas comunes
- Short-circuit in the motor or motor cable
- Brief fault leading to current exceeding KPP maximum current
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Review trace recording of axis current for overcurrent events.
- 2
Check the motor for internal faults or winding issues.
- 3
Inspect the motor cable for short-circuits or damage.
- 4
Reinitialize the drive bus by cycling Power Off / Power On.
- 5
Check the KSP module for any status indicators.
- 6
Check the KPP module for any status indicators.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Kuka KR C4 Controller