OC1-Trip (Overcurrent)
Kuka · KR C2 Robot Controller
¿Qué significa 11 ?
This fault indicates an overcurrent condition. For the KPS-600, it specifically signifies an I*t overload of the brake resistor during the charging phase, implying excessive energy dissipation. For KSDs, it means a power unit overcurrent, typically a short-circuit or ground fault detected by hardware monitoring, which is a critical fault risking damage to the power stage.
Causas comunes
- OC1-Trip: Overcurrent detected, phase 1 (P1-01).
- Sudden load increase exceeding motor capacity.
- Short circuit in motor winding or power cable.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the insulation resistance between motor phases U-V, V-W, U-W using a megger at 500VDC — expect >1 MΩ.
- 2
Measure motor current on each phase during operation and compare to motor nameplate Full Load Amperage (FLA).
- 3
Verify that motor parameters (e.g., nominal current, overload limits) stored in the drive match the motor nameplate.
- 4
Inspect the brake resistor for physical damage or signs of overheating, and measure its resistance value.