Platform Load is over 99%
Kone · Elevator Control
¿Qué significa 99 ?
The detected load on the platform exceeds 99% of its rated capacity. This is a warning only, indicating the platform is at its absolute load limit.
Causas comunes
- Platform loaded at or near its maximum capacity.
- Malfunction of the platform overload sensor, providing an inaccurate reading.
- Minor fluctuations in load pushing it over the 99% threshold.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the actual load on the elevator platform against its rated capacity.
- 2
Inspect all wiring and connections for the load weighing system sensors (e.g., load cells) for damage, corrosion, or looseness.
- 3
Check the elevator control system parameters related to load weighing, capacity settings, and calibration values for correct configuration according to manufacturer documentation.
- 4
Verify the physical mounting and integrity of the load weighing sensors to ensure no obstructions or mechanical stress are affecting their measurement.
- 5
Perform a functional test or recalibration of the load weighing system using known weights if the above steps do not resolve the issue, following manufacturer procedures.