CONTACTOR DRIVER
Kone · Elevator Control
¿Qué significa 1075 ?
The motor controller (codes 1075, 2075, 3075) has detected a fault in the main contactor driver circuit. This affects the ability to control the main power contactor. The specific lift reaction is controller dependent.
Causas comunes
- Contactor driver circuit open or shorted.
- Contactor coil fault (e.g., open circuit, short circuit).
- Internal controller hardware failure affecting the driver output.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the auxiliary control voltage supply to the motor controller's contactor driver circuit.
- 2
Inspect wiring and connections between the motor controller's contactor driver output and the main power contactor coil for damage, corrosion, or loose terminals.
- 3
Measure the resistance of the main power contactor coil to confirm it is within the manufacturer's specified range (check for open or short circuit).
- 4
Measure the voltage at the main power contactor coil terminals during a commanded activation attempt to verify the driver's output signal.