82

Overload

Kone · CMXC-022 Frequency Control Upgrade Kit

¿Qué significa 82 ?

An overload situation has been detected by the R&M Materials Handling Frequency Converter, meaning the load on the motor exceeds its rated capacity. This can be caused by excessive physical load, worn mechanical components like the chain drive, or a faulty/miscalibrated load sensor.

Causas comunes

  • Load on hook exceeds the rated load
  • Worn chain or chain drive (in chain hoists)
  • Load sensor is out of calibration
  • Load sensor has failed
  • Mechanical failure in the gear system (in chain hoists)

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify that the load on the hook does not exceed the rated load capacity

  2. 2

    Check and replace the chain and chain drive if worn

  3. 3

    Recalibrate the load sensor by performing the load calibration function

  4. 4

    If the problem recurs after recalibration, replace the load sensor and perform offset correction and calibration

  5. 5

    Check hoist gear operation for unusual noise or vibration, indicating mechanical failure