39

Index Length

Indramat · ServoDyn D Servo Drive

¿Qué significa 39 ?

This error occurs when the system attempts to switch from Manual to Automatic mode, but the amount of material that has passed under the measuring wheel is greater than the configured part length. This implies a discrepancy in material tracking during a mode transition.

Causas comunes

  • The measured material length exceeds the programmed part length when attempting to switch modes.
  • Incorrectly calibrated or malfunctioning measuring wheel encoder.
  • Parameter 21 (Length Correction) is not set correctly, leading to inaccurate material length calculations.
  • Manual material handling or process interruptions causing an unexpected length difference.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify that the index length is correct before attempting to switch from Manual to Automatic mode.

  2. 2

    Refer to Parameter 21 (Length Correction) in Chapter 4 for information on how to properly set and adjust index length.

  3. 3

    Inspect the measuring wheel encoder for proper calibration, physical damage, and accurate material measurement.

  4. 4

    Ensure that the part length parameter in the CLM01.3-M is correctly configured for the application.

  5. 5

    Review the operational procedure for mode switching to ensure it occurs at an appropriate point in the material processing cycle.